GFCI Protection: What It Is and GFCI Requirements by Year

If your SafeSpec inspection report sent you here, the inspector found a receptacle or area of the home without working GFCI protection, or a GFCI device that did not trip when tested. This page covers GFCI requirements by year for St. Louis area homes. It explains what a GFCI does, how it is tested, why older homes often lack it, and the National Electrical Code (NEC) edition that first required it in each part of a house.

What a GFCI Is

GFCI stands for ground fault circuit interrupter. It is a shock protection device built into a receptacle (the outlet with the TEST and RESET buttons) or into a circuit breaker in the electrical panel.

One GFCI receptacle can also protect other ordinary receptacles wired downstream from it, so a plain looking outlet in a bathroom may still be protected by a GFCI in another room or in the garage.

How a GFCI Protects You

Electricity normally flows out on the hot wire and back on the neutral wire in equal amounts. A GFCI watches both sides all the time. If some of that current leaks out another way, such as through a person standing on a wet floor, the amounts no longer match.

According to the U.S. Consumer Product Safety Commission, a GFCI cuts power when the difference is as small as 0.006 amps (6 milliamps), and it does it fast enough to prevent a dangerous shock to the heart.

A GFCI is not the same as a regular circuit breaker. A breaker protects the wiring from overheating. A GFCI protects people.

How Inspectors Test GFCI Outlets

GFCI testing is one part of every SafeSpec home inspection in St. Louis. You can read more about how our inspection process works. Here is what we do at each GFCI location:

  • We press the TEST button on GFCI receptacles and confirm power shuts off, then press RESET to restore it.
  • We use a plug-in tester with a GFCI test button at receptacles in locations where current standards call for protection, including outlets that may be protected by a device somewhere else.
  • We note receptacles that have no protection, devices that do not trip, devices that will not reset, and protected outlets with no way to find the reset point.
  • We do not test GFCI circuit breakers in the panel or receptacles that serve equipment such as refrigerators or sump pumps when tripping them could cause damage or loss of service. Those are noted for the seller or a qualified electrical contractor to check.

Why a plug-in tester may not trip an ungrounded GFCI

One limit worth knowing: a plug-in tester creates its test fault through the ground wire. On a GFCI that has no ground wire (common in older homes), the plug-in tester may not trip it even when the GFCI works. In that case the device’s own TEST button is the correct test.

For more on outlets with no ground wire, see our guide to ungrounded outlets, open grounds and bootleg grounds.

Why an Older Home May Not Have GFCI Protection

GFCI requirements were added to the NEC a few locations at a time starting in the early 1970s. Codes apply to new work at the time it is built or permitted.

A home built in 1980 may have met the code in force then and still have no protection in the kitchen, basement or laundry, because those areas were added later.

GFCI code adoption in Missouri and the St. Louis area

Missouri does not have one statewide residential building code. Each city or county decides which code editions to adopt and when, and some adopt editions years after the NEC is published.

The year listed below is the NEC edition that first included the requirement, not the date it took effect where you live. The St. Louis area includes jurisdictions that adopted these editions on different schedules, so your home’s original requirements depend on its address and permit date.

GFCI Requirements by Year: When Each Location Was First Required

The NEC is published every three years. The table shows the first edition that required GFCI protection for 120 volt receptacles in each dwelling location. Later editions often expanded or reworded these rules.

Location in the homeFirst NEC edition
Outdoor receptacles (the 1971 rule carried a January 1, 1973 effective date)NEC 1971
Receptacles near swimming poolsNEC 1971
BathroomsNEC 1975
GaragesNEC 1978
Spas and hot tubsNEC 1981
Kitchen countertop receptacles within 6 feet of the sinkNEC 1987
Unfinished basementsNEC 1987
Hydromassage (whirlpool) bathtubsNEC 1987
BoathousesNEC 1987
Crawl spacesNEC 1990
Wet bar sinks (countertop receptacles within 6 feet)NEC 1993
Replacement receptacles in any location that now requires GFCINEC 1993
All kitchen countertop receptacles, any distance from the sinkNEC 1996
Laundry and utility sinks (receptacles within 6 feet)NEC 2005
Laundry areas, with or without a sinkNEC 2014
Dishwasher outletsNEC 2014
Within 6 feet of any sink in the homeNEC 2014
Bathtub and shower stall areas (within 6 feet)NEC 2014
Finished basements (all basements, finished or not)NEC 2020
Outdoor outlets, including hardwired equipment, up to 50 ampsNEC 2020
Receptacles up to 250 volts in the listed locations (not only 15 and 20 amp outlets)NEC 2020
All kitchen receptacles, not only those serving the countertopNEC 2023
Appliances such as ranges, wall ovens, clothes dryers and microwavesNEC 2023

Published histories of these rules do not always agree on the exact year for a few items, often because a rule was added in one edition and clarified in the next. Where sources differed, we list the NEC edition year that first contained the requirement.

What to Do About Missing or Failed GFCI Protection

  • Upgrade even if it was not required when the home was built. A home inspection reports on safety, not just on what was legal decades ago. GFCI protection is an inexpensive upgrade that prevents serious shocks in wet and damp areas.
  • Hire a qualified electrical contractor. They can add GFCI receptacles or GFCI breakers, find the existing device protecting a circuit, and replace any GFCI that does not trip or reset.
  • Test your GFCIs monthly. The CPSC recommends pressing TEST at least once a month and after a power outage. If power does not shut off, have the device replaced.
  • Label downstream outlets. Small “GFCI Protected” stickers on protected outlets help anyone find the reset button later.

Frequently Asked Questions

When were GFCI outlets first required?

The NEC first required GFCI protection in the 1971 edition, for outdoor receptacles and receptacles near swimming pools. The outdoor rule carried a January 1, 1973 effective date. Bathrooms were added in the 1975 NEC and garages in the 1978 NEC.

When were GFCI outlets required in kitchens?

The 1987 NEC first required GFCI protection for kitchen countertop receptacles within 6 feet of the sink. The 1996 NEC extended it to all kitchen countertop receptacles, at any distance from the sink. The 2023 NEC covers all kitchen receptacles, not only those serving the countertop.

Does an older home need GFCI outlets if they were not required when it was built?

Codes apply to new work at the time it is built or permitted, so an older home may have met the code in force then. A home inspection reports on safety, not just on what was legal decades ago. GFCI protection is an inexpensive upgrade that prevents serious shocks in wet and damp areas, so we recommend adding it.

How often should I test my GFCI outlets?

The CPSC recommends pressing TEST at least once a month and after a power outage. If power does not shut off, have the device replaced by a qualified electrical contractor.

Why did my GFCI not trip with a plug-in tester?

A plug-in tester creates its test fault through the ground wire. On a GFCI that has no ground wire, common in older homes, the tester may not trip it even when the GFCI works. In that case the device’s own TEST button is the correct test.

Buying a home or have questions about GFCI protection in your report? Schedule your inspection with SafeSpec, call SafeSpec Home Inspections at (314) 375-6014 or email Inspector@SafeSpec.net. We serve St. Louis City and County, St. Charles County and Jefferson County.

Sources